    An automatic load shedding scheme including pumped-storage units

  • Author

    Huang, Shyh-Jier ; Huang, Chin-Chyr

  • Author_Institution
    Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
  • Volume
    15
  • Issue
    4
  • fYear
    2000
  • fDate
    12/1/2000 12:00:00 AM
  • Firstpage
    427
  • Lastpage
    432
  • Abstract
    An automatic load shedding scheme considering the pumped-storage units at Taiwan Power Company (Taipower) is proposed in this paper. Taipower owns ten pumped-storage units which can be shed with higher priority when operated in pumping mode in order to restore the system frequency. In this way, the amount of customer load required to be shed can be significantly decreased. The system reliability and stability can also be enhanced. In the paper, a load frequency control model is developed. An automatic load shedding scheme that is adaptable to Taipower operation is thus developed. The proposed method has been validated through the utility data and compared with the utility shedding scheme. Test results solidify the feasibility and effectiveness of the proposed method for the applications
  • Keywords
    load shedding; power system reliability; power system stability; pumped-storage power stations; Taipower; Taiwan Power Company; automatic load shedding; customer load; pumped-storage units; pumping mode; system frequency restoration; system reliability enhancement; system stability enhancement; utility shedding; Character generation; Frequency control; Load modeling; Power system protection; Power system relaying; Power system restoration; Reliability; Stability; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.900504
  • Filename
    900504