DocumentCode
1433921
Title
An automatic load shedding scheme including pumped-storage units
Author
Huang, Shyh-Jier ; Huang, Chin-Chyr
Author_Institution
Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
Volume
15
Issue
4
fYear
2000
fDate
12/1/2000 12:00:00 AM
Firstpage
427
Lastpage
432
Abstract
An automatic load shedding scheme considering the pumped-storage units at Taiwan Power Company (Taipower) is proposed in this paper. Taipower owns ten pumped-storage units which can be shed with higher priority when operated in pumping mode in order to restore the system frequency. In this way, the amount of customer load required to be shed can be significantly decreased. The system reliability and stability can also be enhanced. In the paper, a load frequency control model is developed. An automatic load shedding scheme that is adaptable to Taipower operation is thus developed. The proposed method has been validated through the utility data and compared with the utility shedding scheme. Test results solidify the feasibility and effectiveness of the proposed method for the applications
Keywords
load shedding; power system reliability; power system stability; pumped-storage power stations; Taipower; Taiwan Power Company; automatic load shedding; customer load; pumped-storage units; pumping mode; system frequency restoration; system reliability enhancement; system stability enhancement; utility shedding; Character generation; Frequency control; Load modeling; Power system protection; Power system relaying; Power system restoration; Reliability; Stability; Testing; Voltage;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.900504
Filename
900504
Link To Document