• DocumentCode
    1443687
  • Title

    Harmonics produced by direct current in convertor transformers

  • Author

    Yacamini, R. ; de Oliveira, J.C.

  • Author_Institution
    University of Manchester Institute of Science and Technology, Department of Electrical Engineering & Electronics, Manchester, UK
  • Volume
    125
  • Issue
    9
  • fYear
    1978
  • fDate
    9/1/1978 12:00:00 AM
  • Firstpage
    873
  • Lastpage
    878
  • Abstract
    Test and analytical procedures are described that determine the relationship between direct current and resultant harmonics in a convertor transformer. It is shown that a linear relationship exists between lower-order harmonics and direct current. The effect of `fluxing¿ the transformer is also shown, and it is found that `under-fluxing¿ a transformer in the presence of direct current has little effect.
  • Keywords
    current transformers; harmonic analysis; harmonics; magnetic flux; modelling; power convertors; direct current transformer; harmonic analysis; harmonics; magnetic flux; modelling; power convertor; testing;