DocumentCode
1456760
Title
Application of ground-fault neutralizers
Volume
72
Issue
7
fYear
1953
fDate
7/1/1953 12:00:00 AM
Firstpage
606
Lastpage
606
Abstract
GROUND-FAULT NEUTRALIZERS have been applied principally in the range of medium transmission voltages. The effectiveness of ground-fault neutralizers on a system depends on the ratio of single line-to-ground faults in the total number of nonpersisting faults. This ratio is influenced by the transmission-line configuration, the line insulation employed, and the structure-footing resistance if structure downleads are used. Where this ratio has been high, ground-fault neutralizers have provided an excellent record in reducing line outages 80 to 90 per cent.
Keywords
Circuit faults; Fault currents; Insulation; Power cables; Resistance; Wires;
fLanguage
English
Journal_Title
Electrical Engineering
Publisher
ieee
ISSN
0095-9197
Type
jour
DOI
10.1109/EE.1953.6438117