• DocumentCode
    1490813
  • Title

    Study of partial discharge charge evaluation and the associated uncertainty by means of high frequency current transformers

  • Author

    Rodrigo, A. ; Llovera, P. ; Fuster, V. ; Quijano, A.

  • Author_Institution
    Inst. Tecnol. de la Energia - Redit, Univ. Politec. de Valencia, Valencia, Spain
  • Volume
    19
  • Issue
    2
  • fYear
    2012
  • fDate
    4/1/2012 12:00:00 AM
  • Firstpage
    434
  • Lastpage
    442
  • Abstract
    High frequency current transformers (HFCT) are widely used in partial discharge field and laboratory tests. Using these devices as sensors in partial discharge cable tests brings some advantages, namely: high degree of insulation, relatively good sensibility and the possibility of broadband measures. This paper analyzes the fundamentals of HFCTs measurements from the point of view of charge evaluation. Three different procedures for charge evaluation and the associated uncertainty are presented for partial discharge measurements in cables by means of HFCTs. Experimental and simulation data are presented and the associated uncertainty is calculated.
  • Keywords
    current transformers; high-frequency transformers; partial discharge measurement; power cables; transformer insulation; HFCT measurement; broadband measures; charge evaluation; high frequency current transformer; partial discharge cable tests; partial discharge charge evaluation; partial discharge measurement; Calibration; Current measurement; Equations; Mathematical model; Partial discharges; Pulse measurements; Uncertainty; Partial discharges; charge measurement; high frequency current transformers; uncertainty;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2012.6180236
  • Filename
    6180236