DocumentCode
1498576
Title
Deadbeat control method for single-phase UPS inverters with compensation of computation delay
Author
Kukrer, O. ; Komurcugil, H.
Author_Institution
Dept. of Electr. & Electron. Eng., Eastern Mediterranean Univ., Mersin, Turkey
Volume
146
Issue
1
fYear
1999
fDate
1/1/1999 12:00:00 AM
Firstpage
123
Lastpage
128
Abstract
In existing deadbeat control techniques for single-phase UPS inverters, the pulse width of the inverter output voltage is limited by the computation time of the controlling processor. This limits the utilisation of the DC source voltage and slows the response of the control system. A deadbeat control technique is presented which eliminates these limitations by allowing the application of the newly computed pulse width with time delay. During this delay, the previously applied pulse width is preserved until it is updated by the new pulse width. This method requires the use of a load-dependent reference function for the inverter output voltage. However, the error in the load voltage caused by using a fixed reference function is shown to be negligible. Computer simulations are performed to verify the theoretical results and for comparison with existing methods. Experimental results are also presented to support the theoretical considerations
Keywords
PWM invertors; compensation; uninterruptible power supplies; voltage control; DC source voltage utilisation; computation delay; control system response; deadbeat control method; inverter output voltage; inverter output voltage pulse width; load-dependent reference function; single-phase UPS inverters;
fLanguage
English
Journal_Title
Electric Power Applications, IEE Proceedings -
Publisher
iet
ISSN
1350-2352
Type
jour
DOI
10.1049/ip-epa:19990215
Filename
757962
Link To Document