• DocumentCode
    1503037
  • Title

    Cascaded Nine-Level Inverter for Hybrid-Series Active Power Filter, Using Industrial Controller

  • Author

    Varschavsky, Alexander ; Dixon, Juan ; Rotella, Mauricio ; Morán, Luis

  • Author_Institution
    CGE Distribucion S.A. Teatinos, Santiago, Chile
  • Volume
    57
  • Issue
    8
  • fYear
    2010
  • Firstpage
    2761
  • Lastpage
    2767
  • Abstract
    An industrial controller, specifically designed for two- and three-level converters, was adapted to work on an asymmetrical nine-level active power filter (APF). The controller is now able to make all required tasks for the correct operation of the APF, such as current-harmonic elimination and removal of high-frequency noise. The low switching-frequency operation of the nine-level converter was an important advantage in the application of the industrial controller. In addition, with the nine-level filter, switching losses were significantly reduced. The filter was designed to work as voltage source and operates as harmonic isolator, improving the filtering characteristics of the passive filter. The control strategy for detecting current harmonics is based on the “ p-q theory ” and the phase-tracking system in a synchronous reference frame phase-locked loop. The dc-link voltage control is analyzed together with the effect of controller gain and delay time in the system´s stability. Simulations for this application are displayed and experiments in a 1-kVA prototype, using the aforementioned industrial controller, were tested, validating the effectiveness of this new application.
  • Keywords
    active filters; delays; electric current control; harmonic distortion; industrial control; invertors; passive filters; phase locked loops; power filters; switching convertors; voltage control; DC-link voltage control; apparent power 1 kVA; asymmetrical nine-level active power filter; cascaded nine-level inverter; controller gain; current harmonic detection; current harmonic elimination; delay time; harmonic distortion; harmonic isolator; high-frequency noise removal; hybrid-series active power filter; industrial controller; low switching-frequency operation; p-q theory; passive filter; phase-tracking system; switching losses; synchronous reference frame phase-locked loop; system stability; three-level converters; two-level converters; Active filters; harmonic distortion; multilevel systems; power quality;
  • fLanguage
    English
  • Journal_Title
    Industrial Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0278-0046
  • Type

    jour

  • DOI
    10.1109/TIE.2009.2034185
  • Filename
    5290089