DocumentCode
1515492
Title
Verification of an alternating current corona model for use as a current transmission line design aid
Author
Rickard, D.A. ; Dupuy, J. ; Waters, R.T.
Author_Institution
Sch. of Electr., Electron. & Syst. Eng., Wales Univ., UK
Volume
138
Issue
5
fYear
1991
fDate
9/1/1991 12:00:00 AM
Firstpage
250
Lastpage
258
Abstract
A controlled laboratory experiment was performed to measure many corona parameters for variable frequency alternating voltage excitation of a coaxial electrode system. A dynamic corona model was implemented in a new computer program and further developed to allow direct comparison with the measured data. Initial agreement was excellent, and a thorough investigation of sensitivity to parameter variations was conducted allowing an optimum fit to be obtained. The model was subsequently used as an aid to the interpretation of experimental waveforms and predictions of the corona performance of real line conductors.
Keywords
corona; overhead line conductors; power overhead lines; power system CAD; alternating current corona model; coaxial electrode system; computer program; corona performance; current transmission line; design aid; dynamic corona model; high-voltage lines; overhead lines; real line conductors; sensitivity to parameter variations; variable frequency alternating voltage excitation;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings A
Publisher
iet
ISSN
0960-7641
Type
jour
Filename
93777
Link To Document