DocumentCode
1516514
Title
Transmission line fault location for phase-to-earth fault using one-terminal data
Author
Zhang, Q. ; Zhang, Y. ; Song, W. ; Yu, Y.
Author_Institution
Dept. of Electr. Power & Autom., Tianjin Univ., China
Volume
146
Issue
2
fYear
1999
fDate
3/1/1999 12:00:00 AM
Firstpage
121
Lastpage
124
Abstract
An accurate algorithm for the fault location of a single phase-to-earth fault on a two-parallel power transmission line is presented. The faulted phase circuit and the zero-sequence circuit of the two-parallel line are used as a fault location model, in which the source impedance of the remote end is not involved. The algorithm effectively eliminates the effect of load flow and fault resistance on the accuracy of fault location. It embodies an accurate fault location by measuring only local data and is used in a procedure that provides the automatic determination of faulted types and phases, rather than requiring an engineer to specify them. Simulation results have demonstrated the validity of the algorithm under the condition of a phase-to-earth fault
Keywords
earthing; fault location; power transmission faults; power transmission lines; transmission network calculations; automatic fault determination; fault location algorithm; single phase-to-earth fault; source impedance; two-parallel power transmission line; zero-sequence circuit;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19990174
Filename
768643
Link To Document