DocumentCode
1517039
Title
Operating partial core transformers under liquid nitrogen conditions
Author
Liew, M.C. ; O´Neill, M.B. ; Bodger, P.S.
Author_Institution
Dept. of Electr. & Electron. Eng., Canterbury Univ., Christchurch, New Zealand
Volume
148
Issue
4
fYear
2001
fDate
7/1/2001 12:00:00 AM
Firstpage
293
Lastpage
298
Abstract
A reverse design method has been applied to partial core transformers. Three sample transformers were built and then tested under liquid nitrogen (N2) conditions. The measured results were compared to model calculated values and the differences used to modify the reverse design model in order to more accurately determine the calculated equivalent circuit parameters. A fourth transformer was then designed, built and tested. The measured performance of this transformer confirmed the validity and accuracy of the model, and showed the usefulness of the reverse design approach
Keywords
cryogenics; equivalent circuits; power transformers; reverse engineering; transformer cores; equivalent circuit parameters; liquid nitrogen conditions; partial core transformer operation; reverse design method;
fLanguage
English
Journal_Title
Electric Power Applications, IEE Proceedings -
Publisher
iet
ISSN
1350-2352
Type
jour
DOI
10.1049/ip-epa:20010438
Filename