DocumentCode
1551639
Title
Effects of Conductor Counter-Transposition on the Positive-Sequence Impedance and Losses of Cross-Bonded Cables
Author
De León, Francisco ; Márquez-Asensio, Manuel L. ; Álvarez-Cordero, Gabriel
Author_Institution
Polytech. Inst., New York Univ., New York, NY, USA
Volume
26
Issue
3
fYear
2011
fDate
7/1/2011 12:00:00 AM
Firstpage
2060
Lastpage
2063
Abstract
In this letter, we show that contrary to common belief, counter-transposing the conductors when power cables are cross-bonded can increase the positive-sequence resistance by close to 20%. This is very important because the losses of a power cable are determined (for balanced operation) from the Joule loasses caused by the positive-sequence resistance (3R1I12).
Keywords
conductors (electric); losses; power cables; Joule loasses; conductors; counter transposition; cross-bonded cables; positive-sequence resistance; power cables; Cable shielding; Conductors; Equations; Impedance; Power cables; Resistance; Wires; Ampacity; cable parameters; cables; cross-bonding; losses; positive-sequence impedance; resistance;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2011.2123473
Filename
5872034
Link To Document