• DocumentCode
    1569550
  • Title

    Effect of single phase to ground fault with arc resistance on the performance of distance relay

  • Author

    Taghizadeh, Majid ; Sadeh, Javad ; Bashir, Mohsen ; Kamyab, Ebadollah

  • Author_Institution
    Ferdowsi Univ. of Mashhad Mashhad, Mashhad, Iran
  • fYear
    2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Distance relay is the main protection of power transmission lines and make an important role in power system stabilization if it operates selective and instantaneous. In this paper, the trajectory of the fault impedance is determined. It is shown that in the end of the first zone or in the middle of the second zone, distance relay could not make a correct decision for operating if the fault occurs with arc. So to overcome this problem, in this paper a novel technique using total harmonic distortion (THD) is proposed. The proposed method makes the distance relay more selective and instantaneous.
  • Keywords
    arcs (electric); earthing; electric impedance; harmonic distortion; power system harmonics; power system stability; power transmission lines; relay protection; THD; arc resistance; distance relay; fault impedance; ground fault; power system stabilization; power transmission line protection; single phase effect; total harmonic distortion; Circuit faults; Equations; Impedance; Mathematical model; Protective relaying; Solids; Arcing faults; Distance protection; Fast Fourier analysis; Total harmonic distortion;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Environment and Electrical Engineering (EEEIC), 2011 10th International Conference on
  • Conference_Location
    Rome
  • Print_ISBN
    978-1-4244-8779-0
  • Type

    conf

  • DOI
    10.1109/EEEIC.2011.5874587
  • Filename
    5874587