Fast detector of symmetrical fault during power swing for distance relay
Author
Su, B. ; Dong, X.Z. ; Bo, Z.Q. ; Sun, Y.-Z. ; Caunce, B.R.J. ; Tholomier, D. ; Apostolov, A.
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear
2005
Firstpage
1836
Abstract
Distance relay should be blocked during power swing to ensure the reliability, but still should trip as soon as possible after an internal fault occurs during power swing. It was very difficult to detect the symmetrical fault reliably and fast during power swing with complex power swing conditions and fault conditions considered. This paper presents a new fast detector of symmetrical fault during power swing. Based on the sudden reduction of absolute value of the change rate of power swing centre voltage (PSCV), the presented detector can detect the symmetrical fault reliably and sensitively in two cycles. This detector is easy to set and immune to the swing period, fault arc, fault location and power angle. EMTP simulations and real-time digital simulator system (RTDS) tests prove the presented detector is fast, sensible and reliable.
Keywords
fault diagnosis; power transmission faults; power transmission protection; relays; EMTP; distance relay; fault; fault arc; fault location; power angle; power swing; power swing centre voltage; real-time digital simulator system; swing period; symmetrical fault detection; Arc discharges; Detectors; EMTP; Fault detection; Fault location; Power system reliability; Protective relaying; Real time systems; System testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2005. IEEE
Print_ISBN
0-7803-9157-8
Type
conf
DOI
10.1109/PES.2005.1489209
Filename
1489209
Link To Document