• DocumentCode
    1578342
  • Title

    Evaluation of the variations of short-circuit capacities along a feeder due to distribution network upgrading

  • Author

    Chen, T.-H. ; Huang, W.T.

  • Author_Institution
    Dept. of Electr. Eng., Nat. Taiwan Univ. of Sci. & Technol., Taipei, Taiwan
  • fYear
    2005
  • Firstpage
    2536
  • Abstract
    The variations of short-circuit capacities (SCC´s) along a feeder while a primary network is upgraded from original radial to normally closed-loop arrangement is essential for examining the protection system of the network after upgraded. The increments of SCC´s along a feeder may cause the existing protection devices installed at the original network and its customers´ distribution systems becoming inadequate. Hence, a simple, systematic and straightforward evaluation method is required, especially in the planning stage. To meet these requirements the short-circuit MVA method was adopted in this paper. Based on the adopted method, the variations of SCC´s along a primary feeder before and after the network upgraded were represented by simple formulas and illustrated by figures that make the variations more easily be recognized. The results confirm that the short-circuit MVA method is quite suitable for evaluating the variations of SCC´s along a feeder.
  • Keywords
    closed loop systems; power distribution protection; closed-loop arrangement; distribution network upgrading; protection system; short-circuit capacities; Circuit faults; Cities and towns; Councils; Frequency; Integrated circuit interconnections; Power system planning; Protection; Statistical distributions; Substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2005. IEEE
  • Print_ISBN
    0-7803-9157-8
  • Type

    conf

  • DOI
    10.1109/PES.2005.1489426
  • Filename
    1489426