Title
ATP-EMTP study of adjustable speed drive dc link properties during voltage sags
Author
Connell, Robert M O ; Kirawanich, Phumin
Author_Institution
Dept. of Electr. Eng., Missouri Univ., Columbia, MO, USA
fYear
2005
Firstpage
2548
Abstract
ATP-EMTP simulations of a 3-phase commercial power distribution system containing adjustable speed drive (ASD) driven induction motors in the presence of single-line-to-ground and balanced three-phase voltage sags are described. The simulations show both the dynamic influence of the motor on the temporal evolution of certain sags and the peak ASD dc link voltage and current as functions of fault type, location, and duration. The results show that dc link recovery currents can be several times larger than their nominal values, and that the most severe effect occurs during and after a long (1000 msec) three phase fault at an electrically remote location.
Keywords
EMTP; fault location; induction motor drives; power distribution faults; power supply quality; variable speed drives; 3-phase commercial power distribution system; ATP-EMTP study; adjustable speed drive; dc link properties; fault location; induction motors; single-line-to-ground sags; three-phase voltage sags; voltage sags; Circuit faults; Circuit simulation; DC motors; Induction motors; Power distribution; Power quality; Protection; Synchronous motors; Variable speed drives; Voltage fluctuations;