DocumentCode
1584827
Title
Study on electrical tree growth in XLPE by PD patterns
Author
Wu, Guangning ; Park, Dae-Hee
Author_Institution
Sch. of Electr. Eng., Wonkwang Univ., South Korea
Volume
4
fYear
1999
fDate
6/21/1905 12:00:00 AM
Firstpage
272
Abstract
Exploitation of equipment with cross linked polyethylene (XLPE) insulation requires its condition monitoring and diagnostics. Traditionally, diagnostics of insulation is carried out by means of partial discharge detection. Many researchers have developed a lot of methods to identify the defect by the PD form. However, such identification of a defect, for example, void, inclusion or treeing, does not say about its danger from a point of view of full insulation gap breakdown and insulation construction failure. The information about the form and size of formed upon high voltage treeing is necessary for prediction of the remaining resource of XLPE insulation. For this purpose we carry out experimental research for determination of the dependencies between PD characteristics in XLPE upon time and three dimension PD patterns of corresponding treeing. The investigations were carried out by means of electrical measurement of PD current and simultaneous optical recording of treeing image. Test results show that the PD patterns can be applied to detecting tree growth well
Keywords
XLPE insulation; PD current measurement; PD patterns; XLPE; condition monitoring; cross linked polyethylene insulation; diagnostics; electrical tree growth; full insulation gap breakdown; insulation construction failure; optical recording; treeing image recording;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990845
Filename
821273