DocumentCode
1594340
Title
Unified constant-frequency integration control of three-phase active-power-filter with vector operation
Author
Qiao, Chongming ; Jin, Taotao ; Smedley, Keyue M.
Author_Institution
Dept. of Electr. & Comput. Eng., California Univ., Irvine, CA, USA
Volume
3
fYear
2001
fDate
6/23/1905 12:00:00 AM
Firstpage
1608
Abstract
In this paper, a unified constant-frequency integration control (UCI) scheme is proposed for a three-phase active power filter (APF). The proposed control method eliminates the need of sensing the three-phase load current, the nontrivial task of calculating the harmonics and reactive current components, as well as the use of any multipliers, as required by previously reported control methods. By applying one-cycle control and sensing the mains line current, unity power factor and low input current distortion can be realized by one integrator with reset along with a few linear and logic components such as flip-flops, comparators, and clock. All findings are supported by experimental results
Keywords
active filters; control system synthesis; electric current measurement; harmonic distortion; power factor correction; power harmonic filters; voltage control; integrator; low input current distortion; mains line current sensing; one-cycle control; three-phase active power filter; unified constant-frequency integration control; unity power factor; Active filters; Converters; Home appliances; Logic; Power conversion; Power generation; Power harmonic filters; Power system harmonics; Reactive power; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Specialists Conference, 2001. PESC. 2001 IEEE 32nd Annual
Conference_Location
Vancouver, BC
ISSN
0275-9306
Print_ISBN
0-7803-7067-8
Type
conf
DOI
10.1109/PESC.2001.954349