• DocumentCode
    1595541
  • Title

    Pole proximity effect on EL CID results

  • Author

    Ridley, G.K.

  • Author_Institution
    ADWEL Int. Ltd., Canada
  • fYear
    1997
  • Firstpage
    346
  • Lastpage
    350
  • Abstract
    A three-dimensional finite element analysis of the magnetic field between the stator and rotor of salient-pole hydroelectric generators has shown quantitatively that end leakage flux produces distortion of EL CID (Electromagnetic Core Imperfection Detector) results, which are obtained relatively close to the side of a pole piece. The conclusion is in agreement with results obtained from two test cases. This was expected for the first machine, but a careful reappraisal of the test results for the second machine was required to establish a correlation with the 3D-FE analysis, as a pole proximity effect had not been obvious initially. The further conclusion is that EL CID results obtained with the rotor in-situ would inevitably be subject to distortion due to the pole proximity effect. Recognition of this permits it to be taken into account
  • Keywords
    hydroelectric generators; 3-D finite element analysis; electromagnetic core imperfection detector; end leakage flux; magnetic field; pole proximity effect; rotor; salient-pole hydroelectric generators; stator;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electrical Machines and Drives, 1997 Eighth International Conference on (Conf. Publ. No. 444)
  • Conference_Location
    Cambridge
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-696-2
  • Type

    conf

  • DOI
    10.1049/cp:19971096
  • Filename
    677144