• DocumentCode
    1596893
  • Title

    DE algorithm based comparison between two different combinations of FACTS devices under single line outage contingency condition

  • Author

    Jebaraj, L. ; Muralikrishnan, N. ; Rajan, C.Christober Asir

  • Author_Institution
    Department of EEE, Anne´´s College of Engg. and Tech., Panruti, Tamil Nadu, India
  • fYear
    2013
  • Firstpage
    158
  • Lastpage
    165
  • Abstract
    This paper proposes to run the Newton-Raphson load flow program with two different combinations of FACTS devices (TCSC with SVC and SSSC with SVC) separately and compare the results behind the voltage stability limit improvement and active power loss minimization scenario. The line based voltage stability indicator is used for voltage stability assessment. Differential Evolution (DE) algorithm is exploited for optimization of the voltage stability limit, active power loss and location and size of FACTS devices. The effectiveness of the proposed algorithm is validated by carrying out on the standard IEEE 30 bus system under single line outage contingency conditions.
  • Keywords
    Ions; Jacobian matrices; Power capacitors; Thyristors; Differential Evolution Algorithm (DEA); FACTS Devices; Line Stability Index; Load Flow; Static Synchronous Series Compensator (SSSC); Static Var Compensator (SVC); Thyristor Controlled Series Compensator (TCSC); Voltage Stability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Intelligent Systems and Control (ISCO), 2013 7th International Conference on
  • Conference_Location
    Coimbatore, Tamil Nadu, India
  • Print_ISBN
    978-1-4673-4359-6
  • Type

    conf

  • DOI
    10.1109/ISCO.2013.6481141
  • Filename
    6481141