DocumentCode
1596893
Title
DE algorithm based comparison between two different combinations of FACTS devices under single line outage contingency condition
Author
Jebaraj, L. ; Muralikrishnan, N. ; Rajan, C.Christober Asir
Author_Institution
Department of EEE, Anne´´s College of Engg. and Tech., Panruti, Tamil Nadu, India
fYear
2013
Firstpage
158
Lastpage
165
Abstract
This paper proposes to run the Newton-Raphson load flow program with two different combinations of FACTS devices (TCSC with SVC and SSSC with SVC) separately and compare the results behind the voltage stability limit improvement and active power loss minimization scenario. The line based voltage stability indicator is used for voltage stability assessment. Differential Evolution (DE) algorithm is exploited for optimization of the voltage stability limit, active power loss and location and size of FACTS devices. The effectiveness of the proposed algorithm is validated by carrying out on the standard IEEE 30 bus system under single line outage contingency conditions.
Keywords
Ions; Jacobian matrices; Power capacitors; Thyristors; Differential Evolution Algorithm (DEA); FACTS Devices; Line Stability Index; Load Flow; Static Synchronous Series Compensator (SSSC); Static Var Compensator (SVC); Thyristor Controlled Series Compensator (TCSC); Voltage Stability;
fLanguage
English
Publisher
ieee
Conference_Titel
Intelligent Systems and Control (ISCO), 2013 7th International Conference on
Conference_Location
Coimbatore, Tamil Nadu, India
Print_ISBN
978-1-4673-4359-6
Type
conf
DOI
10.1109/ISCO.2013.6481141
Filename
6481141
Link To Document