Author
Dán, András ; Raisz, Dávid
Author_Institution
Dept. of Electr. Power Eng., Power Syst. & Environ. Group, Budapest Univ. of Technol. & Econ., Budapest, Hungary
fYear
2010
Firstpage
237
Lastpage
242
Abstract
The first part of this paper contains a short review on single phase to earth fault location methods in compensated networks. After that a new fault location method is presented that has been implemented recently at Hungarian DSOs. This technique uses current injection parallel to the Petersen coil, and the same device is further used to decrease the harmonics in the residual fault current during sustained earth-fault operation. First field test results are also shown.
Keywords
earthing; fault currents; fault location; harmonics suppression; Hungarian DSO; Petersen coil; compensated networks; current injection technique; earth fault location method; residual fault current; single phase fault location methods; Analytical models; Earth; Fault location; Fault tolerance; Hardware design languages; Information analysis; Information technology; Microcontrollers; Microprocessors; Transient analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Power Quality and Supply Reliability Conference (PQ), 2010
Conference_Location
Kuressaare
Print_ISBN
978-1-4244-6978-9
Type
conf
DOI
10.1109/PQ.2010.5549990
Filename
5549990
Link To Document