DocumentCode
1622742
Title
Effects of SMES on dynamic behaviors of type D-Wind Turbine Generator-Grid connected during short circuit
Author
Yunus, A. M Shiddiq ; Abu-Siada, A. ; Masoum, M.A.S.
Author_Institution
Dept. of Mech. Eng., State Polytech. of Ujungpandang, Makassar, Indonesia
fYear
2011
Firstpage
1
Lastpage
6
Abstract
Application of Superconducting Magnetic Energy Storage unit with Hysteresis Current Control-Fuzzy Logic to improve the performance of Wind Turbine Generator-Grid connected during short circuit is presented. Five 2 MW Type D-Wind Turbine Generator connected to a grid is simulated using SIMULINK/MATLAB program. The Superconducting Magnetic Energy Storage unit consists of a Voltage Source Converter and DC-DC Chopper that are controlled by Hysteresis Current Control and Fuzzy Logic Controller respectively. Simulation results show that the proposed control algorithm of Superconducting Magnetic Energy Storage unit is effective in saving some MWs of Type D-Wind Turbine Generator production during occurrence of short circuit in the line.
Keywords
DC-DC power convertors; choppers (circuits); electric current control; fuzzy control; power generation control; power grids; wind turbines; DC-DC chopper; SMES; Simulink-Matlab program; hysteresis current fuzzy logic control; power 2 MW; short circuit; superconducting magnetic energy storage unit; type D-wind turbine generator-grid; voltage source converter; Choppers; Circuit faults; Coils; Generators; Superconducting magnetic energy storage; Voltage control; Wind turbines; Fuzzy Logic; Hysteresis Current Control Superconducting magnetic energy storage; Type D-Wind Turbine Generator;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2011 IEEE
Conference_Location
San Diego, CA
ISSN
1944-9925
Print_ISBN
978-1-4577-1000-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2011.6039276
Filename
6039276
Link To Document