DocumentCode
164753
Title
Monitoring of dips in the MV network for regulation- A case study
Author
Weldemariam, L.E. ; Cuk, V. ; Cobben, J.F.G. ; Kling, W.L.
Author_Institution
Dept. of Electr. Eng., Eindhoven Univ. of Technol., Eindhoven, Netherlands
fYear
2014
fDate
25-28 May 2014
Firstpage
526
Lastpage
530
Abstract
Voltage dips constitute to a noticeable part of power quality (PQ) problems but causing major financial losses to industrial and commercial customers. This work involves comparative studies to choose the most appropriate location of monitoring dips for regulation. In this paper, a Dutch MV network is used and dip monitoring locations are considered at different points of connections (POC) where customers are connected. To estimate the number of dips per year, simulations are performed on the network using PowerFactory. The voltage dip profiles at the selected monitoring point are analyzed for phase and line voltage dips. The effects of distributed generation (DG) on the voltage dips are also observed and the transfer of voltage dips from MV to LV network is briefly discussed. To analyze the effects of the expected dips on industrial equipment, severity curves are applied onto the standard dip tables.
Keywords
distributed power generation; power supply quality; Dutch MV network; LV network; PowerFactory; dip monitoring locations; distributed generation; financial losses; industrial equipment; points of connections; power quality problems; standard dip tables; voltage dip profiles; Electronics packaging; Generators; Monitoring; Power cables; Power quality; Standards; Voltage fluctuations; distributed generation; monitoring dips; point of connection; power quality; voltage dip;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
Conference_Location
Bucharest
Type
conf
DOI
10.1109/ICHQP.2014.6842916
Filename
6842916
Link To Document