• DocumentCode
    1680142
  • Title

    Electric fields in 400 kV transmission lines

  • Author

    Keikko, T. ; Isokorpi, J. ; Korpinen, L.

  • Author_Institution
    Electr. Power Eng., Tampere Univ. of Technol., Finland
  • fYear
    1999
  • Firstpage
    57
  • Abstract
    The 400 kV transmission line electric field was measured, and these results were compared to the guidelines. Transmission lines were measured in surroundings of Tampere, Helsinki and Paimio for 25 spans with 38 measurements. In the study, the measured electric field values did exceed the 5 kV/m guideline for general public exposure by ICNIRP in 10 measured spans. The aim of this study was to compare measured 400 kV transmission line electric fields to the guidelines.
  • Keywords
    electric field measurement; electric fields; power transmission lines; 400 kV; Finland; electric field measurements; power transmission lines; public exposure guidelines; Electric variables measurement; Guidelines; Magnetic field measurement; Power engineering and energy; Power measurement; Power transmission lines; Transmission line measurements; Transmission lines; Vegetation; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
  • Conference_Location
    Budapest, Hungary
  • Print_ISBN
    0-7803-5836-8
  • Type

    conf

  • DOI
    10.1109/PTC.1999.826488
  • Filename
    826488