• DocumentCode
    1683925
  • Title

    Permissible current rating of the investigated 110 kV underground cable line

  • Author

    Sredojevic, M.R. ; Popovic, Dj.P. ; Simic, M.D.

  • Author_Institution
    Electr. Eng. Inst., Belgrade, Yugoslavia
  • fYear
    1999
  • Firstpage
    218
  • Abstract
    This paper analysis the influence of the soil kind and its drying out on the permissible current rating of a 110 kV underground cable line, located in Belgrade area. The analysis is carried out by means of modified mathematical model of IEC Publication 287 and the results of long term test investigations of the local soil thermal behavior along the cable route. The soil around the cables is treated with simplified physical model. It is supposed that the local soil along the cable route consists from two layers with different kinds and diameters of the dried out soil zone around 110 kV single-core cables in trefoil formation.
  • Keywords
    power cable testing; soil; underground cables; 110 kV; IEC Publication 287; local soil thermal behavior; mathematical model; permissible current rating; single-core cables; soil drying; trefoil formation; underground cable lines; Cables; Conducting materials; Conductivity; Mathematical model; Moisture; Soil; Surface resistance; Temperature; Testing; Thermal resistance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
  • Conference_Location
    Budapest, Hungary
  • Print_ISBN
    0-7803-5836-8
  • Type

    conf

  • DOI
    10.1109/PTC.1999.826650
  • Filename
    826650