DocumentCode
1704896
Title
Setting Calculation of the Directional Relays Considering Dynamic Changes in the Network Topology
Author
Yang, Xiongping ; Shi, Dongyuan ; Duan, Xianzhong
Author_Institution
Coll. of Electr. & Electron. Eng., HuaZhong Univ. of Sci. & Technol., Wuhan
fYear
2006
Firstpage
1
Lastpage
6
Abstract
Identifying some typical and critical system conditions is an important and key step in conducting setting calculation of the directional relays. Under these normal operation or contingency conditions, fault calculation is performed to determine the suitable settings or check relay performance such that their fundamental protective objectives are met for a variety of system configurations and conditions. This paper analyzes the impact of dynamic change of network topology on the relay setting, which includes line outages, breaking of loops and operation mode switching of power substations or plants. Electrical coupling indices of loops are introduced to determine the break-loop lines, whose outage will result in great impact on the distribution of fault current. In addition, sensitivity factors are derived for determining the substations or plants and their corresponding operation modes which have the greatest potential impact on the fault current magnitude. Examples are presented to verify the validity and simplicity of the proposed methods.
Keywords
distribution networks; relay protection; transmission networks; directional relays; fault calculation; fault current distribution; network topology; Fault currents; Mesh networks; Network topology; Power system dynamics; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Substation protection; Breaking of loops; Fault current; Network topology; Operation mode switching; Power system; Relay coordination;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2006. PowerCon 2006. International Conference on
Conference_Location
Chongqing
Print_ISBN
1-4244-0110-0
Electronic_ISBN
1-4244-0111-9
Type
conf
DOI
10.1109/ICPST.2006.321572
Filename
4116119
Link To Document