• DocumentCode
    171884
  • Title

    Identification of the power transformer 110/23 kV failure

  • Author

    Brandt, M. ; Peniak, Adrian

  • Author_Institution
    Dept. of Meas. & Appl. Electr. Eng., Univ. of Zilina, Zilina, Slovakia
  • fYear
    2014
  • fDate
    19-20 May 2014
  • Firstpage
    531
  • Lastpage
    534
  • Abstract
    This paper deals with power oil transformer 40 MVA complex diagnostics and its state evaluation. The diagnostic methods like the evaluation of capacitances, loss factor tg δ and analysis of frequency responses by SFRA method were used for identification. These diagnostic methods enable identification of fault by comparative measurements. In this paper is shows identification of short circuit by use of interwinding SFRA measurements.
  • Keywords
    failure analysis; fault diagnosis; frequency response; power transformers; SFRA method; capacitance evaluation; comparative measurements; diagnostic methods; fault identification; frequency response analysis; interwinding SFRA measurements; loss factor; power oil transformer; power transformer failure identification; voltage 110 kV; voltage 23 kV; Area measurement; Capacitance; Capacitance measurement; Frequency measurement; Humidity measurement; Lead; Systems engineering and theory; capacitance; diagnostics; sweep frequency response analysis; transformer;