• DocumentCode
    1722461
  • Title

    Assessment of insulation in aged power transformers and the correlation between the electrical and chemical properties

  • Author

    Darveniza, M. ; Saha, T.K. ; Hill, D.J.T. ; Le, T.T.

  • Author_Institution
    Queensland Univ., St. Lucia, Qld., Australia
  • fYear
    1992
  • Firstpage
    671
  • Lastpage
    678
  • Abstract
    Interfacial polarization and dissipation factor measurements have been made on paper-insulated conductor samples collected from an old retired transformer and on samples which had been subjected to accelerated aging. The molecular weights of the samples were also studied by GPC (gel permeation chromatography) analysis. Good correlation has been obtained between the methods for detecting changes in the properties of the insulation papers. Preliminary results are presented which also show very good correlation between the electrical and chemical test methods
  • Keywords
    ageing; chromatography; dielectric polarisation; insulation testing; life testing; molecular weight; paper; power transformers; transformer insulation; accelerated aging; aged power transformers; chemical properties; dissipation factor; electrical properties; gel permeation chromatography; insulation assessment; interfacial polarization; molecular weights; paper-insulated conductor samples; Accelerated aging; Breakdown voltage; Conductors; Dielectrics and electrical insulation; Gas insulation; Oil insulation; Polarization; Power transformer insulation; Power transformers; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1992. Annual Report. Conference on
  • Conference_Location
    Victoria, BC
  • Print_ISBN
    0-7803-0565-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.1992.283141
  • Filename
    283141