  • Abstract
    Based on the electromagnetic coupling method, a new kind of clamp current sensor was designed to detect partial discharges (PD) in XLPE cable joint. The sensor is a Rogowski coil with a non-crystal core, its bandwidth is located in very high frequency band (VHF) from 1 MHz to 60 MHz. Our test results both in our laboratory and on-site measurement indicated that the sensor is suitable for PD on-site testing and on-line monitoring in XLPE cable joint.
  • Keywords
    VHF devices; XLPE insulation; cable jointing; electric sensing devices; partial discharge measurement; power cable insulation; power cable testing; 1 to 60 MHz; Rogowski coil; VHF sensor; XLPE cable joint; clamp current sensor; electromagnetic coupling method; high frequency band; noncrystal core; on-line monitoring; on-site testing; partial discharge measurement; Cable insulation; Cable shielding; Frequency; Magnetic cores; Magnetic sensors; Partial discharge measurement; Partial discharges; Power cables; Power measurement; VHF circuits;