PD location in power cables using parametric models
Author
Veen, J. ; Van der Wielen, P. C J M
Author_Institution
Eindhoven Univ. of Technol., Netherlands
Volume
2
fYear
2004
Firstpage
711
Abstract
In order to locate partial discharge in power cables, multiple pulses are detected using sensor(s) either installed at a single cable end or at both ends. The difference in arrival times of pulses originating from the same defect provides a measure for the discharge location. Multiple sources contribute to errors in the determined location, such as attenuation and dispersion introduced by the cable. Dispersion implies that the propagation velocity or cable speed is frequency dependent. As a consequence errors are introduced in the mapping of discharge sources along the cable length. Moreover, pulses spread and waveform reference points cannot be well defined, thus impeding accurate time of arrival estimation. Model-based signal processing provides a theoretical framework to deal with such inaccuracies. An efficient model-based method is proposed that enables compensation for dispersion related errors.
Keywords
partial discharges; power cables; sensors; signal processing; waveform analysis; PD location; cable attenuation; discharge source mapping; dispersion related errors; model based signal processing; partial discharge location; power cables; sensors; velocity propagation; waveform reference point; Attenuation; Fault location; Frequency dependence; Impedance; Parametric statistics; Partial discharge measurement; Partial discharges; Power cables; Pulse measurements; Time of arrival estimation;
fLanguage
English
Publisher
ieee
Conference_Titel
Solid Dielectrics, 2004. ICSD 2004. Proceedings of the 2004 IEEE International Conference on
Print_ISBN
0-7803-8348-6
Type
conf
DOI
10.1109/ICSD.2004.1350530
Filename
1350530
Link To Document