    Correlation of the thermal history and level of oxidation with field failure in a primary distribution cable study

  • Author

    Linzey, William G. ; Turner, Noel H. ; Bruning, Armin M. ; Bernstein, Bruce

  • Author_Institution
    Lectomec, Sterling, VA, USA
  • Volume
    1
  • fYear
    1998
  • Firstpage
    105
  • Abstract
    A 206 foot section of XLPE insulated, 13.8 kV, tripler distribution cable that had failed in service was removed and different chemical analyses were performed on the XLPE insulation at several distances from the point of failure. X-ray photoelectron spectroscopy (XPS) was used to determine the changes in the chemical composition of the insulation including detection of oxygen, nitrogen and other elements. Other diagnostic tests included Fourier transform infrared spectroscopy (FTIR), oxidation induction time (OIT) and differential scanning calorimetry (DSC). In addition AC breakdown tests were performed on two 30 foot lengths of a single leg of the cable. A direct correlation was observed between the localized level of oxidation and the magnitude of the local peak temperature seen in service. The location of the point of failure correlated with higher levels of oxidation and correspondingly with a higher local peak temperature. These results suggest that measurement of oxidation products is one tool useful in estimating the degree of degradation in XLPE cable.
  • Keywords
    Fourier transform spectroscopy; X-ray photoelectron spectra; XLPE insulation; differential scanning calorimetry; electric breakdown; insulation testing; oxidation; power cable insulation; power cable testing; spectrochemical analysis; temperature distribution; underground cables; 13.8 kV; 206 feet; 30 feet; AC breakdown tests; Fourier transform infrared spectroscopy; X-ray photoelectron spectroscopy; XLPE cable degradation; XLPE insulated tripler distribution cable; XLPE insulation; chemical analyses; chemical composition; diagnostic tests; differential scanning calorimetry; field failure; local peak temperature; localized oxidation level; oxidation induction time; oxidation level; point of failure; primary distribution cable; thermal history; underground primary distribution cables; Cable insulation; Chemical analysis; Chemical elements; Foot; History; Oxidation; Power cable insulation; Power cables; Temperature; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1998. Conference Record of the 1998 IEEE International Symposium on
  • Conference_Location
    Arlington, VA, USA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-4927-X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1998.704659
  • Filename
    704659