• DocumentCode
    1732300
  • Title

    Load capability of transformers: "Experiences within an actual grid situation"

  • Author

    Nuijten, Jeroen ; Geschiere, Alex

  • Author_Institution
    NUON Tecno - The Netherlands
  • fYear
    2005
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    As the need for energy rises and the pressure is high on maximising network capacity, Nuon wanted to know the maximum load capability of HV/MV-transformers, within actual grid conditions. This research has shown that the maximum load capability of transformers during the winter (based upon Dutch weather conditions) is 120% for two hours. During a failure in the summer the maximum capability is 110%.