DocumentCode
1744618
Title
Maximising rotor thermal capacity
Author
Lachs, W.R.
Author_Institution
Dept. of Electr. Power, New South Wales Univ., Sydney, NSW
Volume
1
fYear
2001
fDate
28 Jan-1 Feb 2001
Firstpage
205
Abstract
Not only is there no uniformity in the method adopted for generator rotor overcurrent protection, but the AVR control algorithms do not directly assess the rotor´s temperature. Often, after rotor overcurrent protection has functioned following a sharp increase of excitation current, 90% of the rotor´s thermal capacity is still unused. A computationally reliable and fast method has been devised for assessing rotor temperature and its rate of change by monitoring each unit´s rotor current and voltage. Important benefits can be gained in system operation by utilising this new method to replace existing rotor overcurrent protections
Keywords
electric current measurement; electric generators; machine protection; machine testing; monitoring; overcurrent protection; rotors; thermal analysis; voltage measurement; AVR control algorithms; current monitoring; excitation current; generator rotor overcurrent protection; rotor temperature assessment; rotor thermal capacity maximisation; voltage monitoring; Control systems; Power generation; Power system interconnection; Power system protection; Reactive power; Rotors; System testing; Temperature control; Thermal stability; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Winter Meeting, 2001. IEEE
Conference_Location
Columbus, OH
Print_ISBN
0-7803-6672-7
Type
conf
DOI
10.1109/PESW.2001.917035
Filename
917035
Link To Document