• DocumentCode
    1759706
  • Title

    Correction of saturated current from measurement current transformer

  • Author

    Ozgonenel, Okan

  • Author_Institution
    Electr. & Electron. Eng. Dept., Ondokuz Mayis Univ., Samsun, Turkey
  • Volume
    7
  • Issue
    7
  • fYear
    2013
  • fDate
    Aug. 2013
  • Firstpage
    580
  • Lastpage
    585
  • Abstract
    The suggested study presents an easy and effective way to compensate for the distorted secondary current of measurement-type current transformers (CTs). The suggested compensating algorithm is based on estimating the magnetising current from a Fröhlich hysteresis approach. The efficiency of the proposed technique was first proved using computer simulations. The prototype compensating device was then tested in a laboratory environment using a 5/1A, 10VA, C0,5 measurement-type CT. The proposed compensation algorithm is dependent on CT burden and X/R ratio of the line where CT is connected. The outcomes of the study demonstrate that the technique is able to reconstruct the secondary current with an acceptable error and can be applied to any measurement-type CT regardless of its size and winding topology.
  • Keywords
    compensation; current transformers; magnetic hysteresis; magnetisation; transformer windings; CT; Fröhlich hysteresis approach; X-R ratio; apparent power 10 VA; compensating algorithm; magnetising current estimation; measurement-type current transformer; saturated current correction; secondary current distorted; winding topology;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IET
  • Publisher
    iet
  • ISSN
    1751-8660
  • Type

    jour

  • DOI
    10.1049/iet-epa.2013.0105
  • Filename
    6585057