DocumentCode
1763225
Title
Circuit-Breaker Automated Failure Tracking Based on Coil Current Signature
Author
Razi-Kazemi, A.A. ; Vakilian, Mehdi ; Niayesh, Kaveh ; Lehtonen, Matti
Author_Institution
Electr. Eng. Dept., Sharif Univ. of Technol., Tehran, Iran
Volume
29
Issue
1
fYear
2014
fDate
Feb. 2014
Firstpage
283
Lastpage
290
Abstract
The online condition assessment of circuit breakers (CBs) has been increasingly requested by power utilities in recent years. Trip and close coil current (CC) signature is an effective and noninvasive parameter in CB online condition monitoring. This paper gives an insight into the impacts of the various failures on the coil current waveform, as well as on the CB operation time. The failures and their causes are categorized based on the outcome of these investigations. Finally, a new algorithm using trip/close CC is proposed to detect the mode and cause of CB incipient failures. In this study, the CC patterns are acquired by measurements carried out on (healthy and faulty) CBs of 72.5-kV and 24-kV rating voltages, having SF6 insulation medium, and are equipped with a spring-drive mechanism.
Keywords
SF6 insulation; circuit breakers; condition monitoring; fault diagnosis; CB online condition monitoring; CB operation time; SF6 insulation medium; circuit-breaker automated failure tracking; close coil current signature; coil current waveform; noninvasive parameter; online condition assessment; power utilities; spring-drive mechanism; voltage 24 kV; voltage 72.5 kV; Circuit breakers; Coils; Feature extraction; Latches; Maintenance engineering; Resistance; Voltage control; Circuit breaker (CB); condition monitoring; fault diagnosis; maintenance;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2013.2276630
Filename
6587111