• DocumentCode
    1774952
  • Title

    PD patterns of stator windings by in-factory experiment on a 10kV motor

  • Author

    Chuanyang Li ; JianCheng Song ; Ailiang Kang ; Lingyan Lin ; Wen Su ; Zhipeng Lei

  • Author_Institution
    Shanxi Key Lab. of Coal Min. Equip. & Safety Control, Taiyuan Univ. of Technol., Taiyuan, China
  • fYear
    2014
  • fDate
    1-5 June 2014
  • Firstpage
    168
  • Lastpage
    171
  • Abstract
    Three types of partial discharge (PD), including slot discharge, corona discharge at the slot exit, and bar-to-bar discharge existing on the surface of the ground wall insulation involving 10kV HV motors were presented in this paper. PD patterns were induced through off-line experiment by using single factor aging stator coils embedded into a real stator core slot. The phase resolved partial discharge (PRPD) representation was adopted to gain the fingerprint characteristics of PDs. The research can provide the basis for the on-line monitoring and fault diagnosis of 10kV HV motors.
  • Keywords
    AC motors; coils; condition monitoring; fault diagnosis; machine insulation; partial discharges; stators; HV motor; PD pattern; PRPD; bar-to-bar discharge; corona discharge; fault diagnosis; fingerprint characteristic; ground wall insulation; high voltage motor; in-factory experiment; off-line experiment; on-line monitoring; partial discharge; phase resolved partial discharge; real stator core slot; single factor aging stator coil; slot discharge; stator winding; voltage 10 kV; Corona; Discharges (electric); Fingerprint recognition; Injuries; Monitoring; Partial discharges; Production facilities; PD patterns; PRPD; on-line monitoring; partial discharge (PD);
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials (ISEIM), Proceedings of 2014 International Symposium on
  • Conference_Location
    Niigata
  • Type

    conf

  • DOI
    10.1109/ISEIM.2014.6870745
  • Filename
    6870745