DocumentCode
1775109
Title
Polarity-reversed voltage pulse propagation analysis for power cable insulation diagnosis
Author
Ozaki, Ryotaro ; Masaki, Shohei ; Saiki, Yuma ; Nakato, Fumiya ; Kadowaki, Kazunori
Author_Institution
Grad. Sch. of Sci. & Eng., Ehime Univ., Matsuyama, Japan
fYear
2014
fDate
1-5 June 2014
Firstpage
461
Lastpage
464
Abstract
Water tree degradation is major problem for power transmission cables. Water treeing is typical of the processes involved in the aging of XLPE cables, and it is known that it causes degradation of insulation performance. To avoid catastrophic failure, a method for localization of this water-treed section is required. We here propose a water-tree detection using polarity-reversed voltage pulses propagation. The polarity-reversed voltage pulses are impulse-like voltages having a exponential tail. We obtained a water tree degradation cable by accelerated deterioration aging test and measured the voltage pulse propagation. The measured pulse waveform involves a signal reflected by non-50 Ω. Although the reflection signal is a small peak, the experimental results qualitatively agreed with calculation results.
Keywords
XLPE insulation; ageing; cable insulation; life testing; power cables; trees (electrical); XLPE cables aging; accelerated deterioration aging test; impulse-like voltages; polarity-reversed voltage pulse propagation analysis; power cable insulation diagnosis; power transmission cables; pulse waveform; reflection signal; water tree degradation cable; water-tree detection; Cable insulation; Impedance; Impedance measurement; Insulators; Reliability; Switches; insulation diagonosis; polarity-reversed; pulse time domain reflectometry; water tree;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials (ISEIM), Proceedings of 2014 International Symposium on
Conference_Location
Niigata
Type
conf
DOI
10.1109/ISEIM.2014.6870818
Filename
6870818
Link To Document