DocumentCode
1778018
Title
The basic law and influencing factor of DC bias distribution in AC power which is near the grounding electrode of 800kV HVDC
Author
Sun Fan ; Xu Guanghu ; Zhang Yuan ; Wu Biao ; Ma QingYong
Author_Institution
Xinjiang Electr. Power Res. Inst., Xinjiang Electr. Power Co. of State Grid, Urumchi, China
fYear
2014
fDate
20-22 Oct. 2014
Firstpage
2417
Lastpage
2421
Abstract
According to the test results of DC bias in hami AC power system when 800kV hami-zhenzhou Transmission on Transmission Line under single pole mode of earth operating way, the basic law of current distribution of AC power is conclude the system, and the influence of AC power network mode to DC bias current distribution is analyzed Suggest to chose 80km as the govern redius and configure the grounding points and grounding modes of AC transformers in AC power network, mean while, offer a proposal for the new site selection of HVDC grounding pole and design.
Keywords
HVDC power transmission; current distribution; earth electrodes; power transformer insulation; AC power network mode; AC transformers; DC bias current distribution; HVDC grounding pole; distance 80 km; earth operating way; grounding modes; grounding points; hami AC power system; hami-zhenzhou transmission; single pole mode; transmission line; voltage 800 kV; Circuit faults; Grounding; HVDC transmission; Power transformers; Substations; Switches; DC bias; Electric potential; HVDC transmission; transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology (POWERCON), 2014 International Conference on
Conference_Location
Chengdu
Type
conf
DOI
10.1109/POWERCON.2014.6993951
Filename
6993951
Link To Document