• DocumentCode
    1778018
  • Title

    The basic law and influencing factor of DC bias distribution in AC power which is near the grounding electrode of 800kV HVDC

  • Author

    Sun Fan ; Xu Guanghu ; Zhang Yuan ; Wu Biao ; Ma QingYong

  • Author_Institution
    Xinjiang Electr. Power Res. Inst., Xinjiang Electr. Power Co. of State Grid, Urumchi, China
  • fYear
    2014
  • fDate
    20-22 Oct. 2014
  • Firstpage
    2417
  • Lastpage
    2421
  • Abstract
    According to the test results of DC bias in hami AC power system when 800kV hami-zhenzhou Transmission on Transmission Line under single pole mode of earth operating way, the basic law of current distribution of AC power is conclude the system, and the influence of AC power network mode to DC bias current distribution is analyzed Suggest to chose 80km as the govern redius and configure the grounding points and grounding modes of AC transformers in AC power network, mean while, offer a proposal for the new site selection of HVDC grounding pole and design.
  • Keywords
    HVDC power transmission; current distribution; earth electrodes; power transformer insulation; AC power network mode; AC transformers; DC bias current distribution; HVDC grounding pole; distance 80 km; earth operating way; grounding modes; grounding points; hami AC power system; hami-zhenzhou transmission; single pole mode; transmission line; voltage 800 kV; Circuit faults; Grounding; HVDC transmission; Power transformers; Substations; Switches; DC bias; Electric potential; HVDC transmission; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology (POWERCON), 2014 International Conference on
  • Conference_Location
    Chengdu
  • Type

    conf

  • DOI
    10.1109/POWERCON.2014.6993951
  • Filename
    6993951