DocumentCode
1804408
Title
A single-phase resonant snubber inverter with fixed timing control for a UPS
Author
Yu, Qinghong ; Nelms, R.M.
Author_Institution
Dept. of Electr. & Comput. Eng., Auburn Univ., AL, USA
Volume
4
fYear
2003
fDate
15-19 June 2003
Firstpage
1633
Abstract
In a UPS, the output voltage of a single-phase inverter is filtered with an LC filter to provide a sinusoidal output voltage. Since this inverter has an inductive load like an inverter for a motor drive, topologies for ZVS inverters utilized for motor drives can also be applied in the UPS application. A single-phase resonant snubber inverter (RSI) for application in a UPS has been developed. Analysis of the RSI in a normalized state plane provided insight into the operation of this ZVS inverter. Based on this analysis, fixed timing control based on the direction of the current flowing through the inductor in the output filter was implemented to control the auxiliary switches in a prototype RSI. The direction of the inductor current was sensed using a secondary winding on the output filter inductor. Experimental results are provided for a 1 kW prototype RSI in a UPS.
Keywords
filters; inductors; resonant invertors; snubbers; switching convertors; timing; uninterruptible power supplies; 1 kW; LC filter; RSI; UPS; ZVS inverters; auxiliary switches; fixed timing control; inductive load; inductor current; motor drive; single-phase resonant snubber inverter; sinusoidal output voltage; Filters; Inductors; Inverters; Motor drives; Prototypes; Resonance; Snubbers; Timing; Uninterruptible power systems; Zero voltage switching;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Specialist Conference, 2003. PESC '03. 2003 IEEE 34th Annual
ISSN
0275-9306
Print_ISBN
0-7803-7754-0
Type
conf
DOI
10.1109/PESC.2003.1217702
Filename
1217702
Link To Document