Diagnosis of stator winding insulation of large generator
Author
Xie, Hengkun ; Bo, Yue ; Yanpeng, Hao
Author_Institution
State Key Lab. of Electr. Insulation for Power Equip., Xi´´an Jiaotong Univ., China
Volume
1
fYear
2003
fDate
1-5 June 2003
Firstpage
274
Abstract
Several new parameters is proposed based on testing results of multistress aging testing of stator bar specimens carried out by using a new developed multistress aging system in our laboratory. The corresponding new parameters, including skewness of partial discharge phase resolved distribution, ultra-wide-frequency characteristic parameters of partial discharge and minimal and average propagation velocities of ultrasonic wave in stator bar insulation, change much more remarkable than the conventional parameters with aging time. Therefore these new parameters could be considered as characteristic parameters for diagnosis of stator insulation of large generators. With these characteristic parameters, authors assessed the insulation condition of actual stator bars replaced from several power plants successfully.
Keywords
ageing; insulation; partial discharges; stators; ultrasonic propagation; diagnosis; generator; multistress aging system; multistress aging testing; partial discharge phase resolved distribution; power plants; propagation velocities; propagation velocity; stator bar insulation; stator bar specimens; stator insulation; stator winding insulation; ultra-wide-frequency characteristic parameters; Aging; Bars; Character generation; Insulation testing; Partial discharges; Power generation; Stator windings; System testing; Temperature; Thermal stresses;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
ISSN
1081-7735
Print_ISBN
0-7803-7725-7
Type
conf
DOI
10.1109/ICPADM.2003.1218405
Filename
1218405
Link To Document