• DocumentCode
    1824777
  • Title

    Diagnosis for oil-immersed insulation using partial discharge due to bubbles in oil

  • Author

    Shiota, H. ; Muto, H. ; Fujii, H. ; Hosokawa, N.

  • Author_Institution
    Adv. Technol. Res. & Dept. Center, Mitsubishi Electr. corp., Hyogo, Japan
  • Volume
    3
  • fYear
    2003
  • fDate
    1-5 June 2003
  • Firstpage
    1120
  • Abstract
    This paper deals with the partial discharge (PD) phenomenon and its use in the detection of small bubbles in oil and application to insulation diagnosis for oil-immersed power transformers. Bubbles in the oil strongly affect the reliability of insulation of oil-immersed power transformers as well as foreign particles. As the first step of the diagnosis of discharges in oil-immersed transformers, we conducted experiments to study the PD phenomena by measuring the PD characteristics and by observing the behavior of bubbles in oil. The experimental results, show that the Φ-q patterns strongly depends on the size of bubble.
  • Keywords
    bubbles; partial discharge measurement; power transformer insulation; power transformers; reliability; transformer oil; Φ-q pattern; bubble size; foreign particle; oil; oil immersed insulation diagnosis; oil-immersed power transformer; partial discharge; reliability; Dielectrics and electrical insulation; Electric fields; Ellipsoids; Oil insulation; Partial discharges; Petroleum; Propulsion; Shape; Stress; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
  • ISSN
    1081-7735
  • Print_ISBN
    0-7803-7725-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.2003.1218620
  • Filename
    1218620