• DocumentCode
    1837466
  • Title

    Ten years of operating experience with a 15000 hp, 6000 r/min adjustable speed drive system

  • Author

    Wood, Barry M. ; King, Cecil M. ; Eriksson, Per L. ; Schleuniger, Josef ; Virtanen, Esa

  • Author_Institution
    Chevron Texaco, Richmond, CA, USA
  • fYear
    2004
  • fDate
    13-15 Sept. 2004
  • Firstpage
    297
  • Lastpage
    308
  • Abstract
    This paper is the sequel to a previous paper presented at the IEEE PCIC conference in 1994 [Wood, B et al., 1995]. The original paper focused on the design, testing, and commissioning of the 15000 hp adjustable speed drive (ASD) system. This paper describes the operating experience of this ASD system during its first ten years of service. Several unplanned trips of the ASD, two failures of the input transformer, failure of the motor lead cables, and overheating of the motor that led to its eventual replacement are discussed. The incidents are described, the root causes are examined, the corrective measures are discussed, and the lessons learned are presented. The success of the ASD in dealing with the many utility voltage disturbances experienced by the refinery electrical system is also addressed.
  • Keywords
    electric motors; petroleum industry; transformers; variable speed drives; 15000 hp; IEEE PCIC conference; adjustable speed drive system; input transformer; motor lead cable failure; refinery electrical system; utility voltage disturbances; Costs; Inductors; Oil insulation; Petroleum; Synchronous motors; System testing; Turbines; USA Councils; Variable speed drives; Wounds;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Technical Conference, 2004. Fifty-First Annual Conference 2004
  • ISSN
    0090-3507
  • Print_ISBN
    0-7803-8698-1
  • Type

    conf

  • DOI
    10.1109/PCICON.2004.1352813
  • Filename
    1352813