DocumentCode
1859423
Title
An alternative test for evaluating transformer-oil deterioration using microwaves
Author
Al-Mously, Salah I. ; Ahmed, Ahmed Y.
Author_Institution
Fac. of Electron. Eng., Nasser Univ., Beni-Walid, Libya
Volume
3
fYear
1999
fDate
1999
Firstpage
884
Abstract
This paper describes the sensitivity of microwaves to the chemical and physical specification variation of a power transformer-oil. The evaluation of a power transformer-oil deterioration by measuring the complex permittivity (complex dielectric constant) in the frequency range of X-band (8.5-10.5 GHz) and Ku-band (17.63-18.07 GHz)is investigated. A completely filled short-circuited waveguide technique is used to perform these measurements. It is shown that the microwave measurement of both the dielectric constant and the loss tangent can be successfully implemented for transformer-oil evaluation. Moreover, the low cost of the measurement set-up together with its simplicity and safety encourage us to recommend it for transformer-oil evaluation rather than the traditional high-voltage measurement techniques
Keywords
dielectric loss measurement; insulation testing; microwave measurement; permittivity measurement; power transformer insulation; transformer oil; 17.63 to 18.07 GHz; 8.5 to 10.5 GHz; Ku-band; X-band; breakdown voltage; chemical specification variation; complex permittivity; filled short-circuited waveguide technique; loss tangent; microwave measurement; microwave sensitivity; physical specification variation; power transformer-oil; transformer-oil deterioration; Chemicals; Dielectric constant; Dielectric loss measurement; Dielectric measurements; Frequency measurement; Performance evaluation; Permittivity measurement; Power measurement; Power transformers; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Microwave Conference, 1999 Asia Pacific
Print_ISBN
0-7803-5761-2
Type
conf
DOI
10.1109/APMC.1999.833735
Filename
833735