DocumentCode
1861687
Title
Fault analysis of advanced series compensated line using S-transform and pattern recognition approach
Author
Dash, P.K. ; Samantaray, S.R. ; Panda, G.
Author_Institution
College of Eng., Bhubaneshwar
fYear
2005
fDate
Nov. 29 2005-Dec. 2 2005
Firstpage
1
Lastpage
484
Abstract
The S-transform (ST) is an extension of wavelet transform which possesses superior property over the latter as the moving functions are fixed with respect to time axis while the localizing scalable Gaussian window dilates and translates. Phase spectrum obtained in this transform is always with respect to fixed reference point and the real and imaginary spectrum can be localized independently. Such a transform with moving and scalable localizing Gaussian window, therefore, provides excellent time localization property for different signals. Utilizing the ST fault current signal is analyzed for an advanced series compensated transmission system. The spectral analysis of the current signals at different fault conditions of the system clearly classifies the faulty phase and faulty section
Keywords
fault location; flexible AC transmission systems; pattern recognition; power transmission faults; spectral analysis; wavelet transforms; Phase spectrum; S-transform; advanced series compensated line; advanced series compensated transmission system; fault analysis; fault current signal; pattern recognition; scalable localizing Gaussian window; spectral analysis; wavelet transform; Neural networks; Pattern analysis; Pattern recognition; Power system protection; Power system transients; Power transmission lines; Signal analysis; Transient analysis; Wavelet analysis; Wavelet transforms; Advanced series compensation; FACTS; S-transform; Wavelet transform; fault analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Conference, 2005. IPEC 2005. The 7th International
Conference_Location
Singapore
Print_ISBN
981-05-5702-7
Type
conf
DOI
10.1109/IPEC.2005.206956
Filename
1627245