DocumentCode
1874782
Title
Simulation of SSR evoked by TCSC for UHVAC transmission system from Yimin to fengtun on RTDS
Author
Xin Zhang ; Yundong Song ; Dan Wang ; Zhiqin Zheng ; Gengyin Li
Author_Institution
State Key Lab. of Alternate Electr. Power Syst., North China Electr. Power Univ., Beijing, China
fYear
2012
fDate
8-9 Sept. 2012
Firstpage
1
Lastpage
7
Abstract
In the beginning, a brief introduction of Yimin-fengtun TCSC equivalent system in 2010 is given and the problem required to be solved is put out consequently. In the second section, after a statement of the close-loop impedance controller, various performances of TCSC involving steady-state and transient-state are investigated and the results of relevant simulation on RTDS are presented. In the last part, the simulation of the equivalent system is accomplished with three kinds of combination of TCSC and FSC. Results show that the possibility of SSR exists when TCSC accessed without SSR depressor. Finally, with the torsion vibration frequencies of 500MW and 600MW shaft are revealed by FFT analysis, the main modalities are presented to provide suggestions for the design of the depression of SSR.
Keywords
HVAC; digital simulation; fast Fourier transforms; power engineering computing; FFT analysis; RTDS; SSR simulation; UHVAC transmission system; Yimin-fengtun TCSC equivalent system; power 500 MW; power 600 MW; steady-state; transient-state; Yimin-fengtun; impedance controller; real time digital simulator(RTDS); sub synchronous resonance(SSR); thyristor controlled series capacitor(TCSC);
fLanguage
English
Publisher
iet
Conference_Titel
Sustainable Power Generation and Supply (SUPERGEN 2012), International Conference on
Conference_Location
Hangzhou
Electronic_ISBN
978-1-84919-673-4
Type
conf
DOI
10.1049/cp.2012.1759
Filename
6493078