DocumentCode
1877442
Title
A method of determining the combination of outage works
Author
Kawahara, K. ; Moriwake, T. ; Kubokawa, J. ; Sasaki, H. ; Asahara, H.
Author_Institution
Fukuyama Univ., Japan
fYear
1993
fDate
7-10 Dec 1993
Firstpage
655
Abstract
In a power system, maintenance works are needed to secure stable power supply, which inevitably causes the outage of power facilities. During maintenance works, a high level of power system reliability must be secured. So far, the outage planning of an electric power system has been made by planning engineers with great experience. However, since the amount of information necessary to handle outage work planning is prohibitively large, it has become difficult to adjust the information by human experts. In order to automatically do it, the authors propose an approach to determine the combination of outage works by using numerical computation methods such as the DC load flow. This approach makes use of an index computed from a quantity of overloaded lines in case of any outage of two lines or a generator. The proposed approach has been applied to a part of the 110 kV transmission line systems of the Chugoku Electric Power Company
Keywords
load flow; maintenance engineering; power system planning; power system reliability; 110 kV; 110 kV transmission line systems; Chugoku Electric Power Company; DC load flow; electric power system; maintenance; numerical computation methods; outage planning; overloaded lines; power system reliability; stable power supply;
fLanguage
English
Publisher
iet
Conference_Titel
Advances in Power System Control, Operation and Management, 1993. APSCOM-93., 2nd International Conference on
Conference_Location
IET
Print_ISBN
0-85296-569-9
Type
conf
Filename
292646
Link To Document