• DocumentCode
    1878940
  • Title

    Partial discharge locating system for GIS

  • Author

    Maekawa, H. ; Masui, H. ; Inujima, H. ; Miyamoto, N.

  • Author_Institution
    Mitsubishi Electr. Corp., Tokyo, Japan
  • fYear
    1993
  • fDate
    7-10 Dec 1993
  • Firstpage
    159
  • Abstract
    Detecting of partial discharges (PD) in gas insulated switchgear (GIS) is an important monitoring process. This paper describes the study of behavior of a surge due to PD in GIS. PD can be detected by detecting the electromagnetic wave radiating from the insulated spacer enclosures, because the coaxial central conductor and the enclosure are not completely in the insulating spacer part. An antenna can detect the electromagnetic wave. By detecting several waves from different propagating paths in the same time, PD location in GIS can be estimated. This system is applied to 500 kV GIS
  • Keywords
    charge measurement; electromagnetic wave propagation; gaseous insulation; magnetic variables measurement; partial discharges; surges; switchgear; 500 kV; GIS; antenna; coaxial central conductor; electromagnetic wave detection; gas insulated switchgear; insulated spacer enclosures; monitoring; partial discharge location;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Advances in Power System Control, Operation and Management, 1993. APSCOM-93., 2nd International Conference on
  • Conference_Location
    IET
  • Print_ISBN
    0-85296-569-9
  • Type

    conf

  • Filename
    292706