DocumentCode
1878940
Title
Partial discharge locating system for GIS
Author
Maekawa, H. ; Masui, H. ; Inujima, H. ; Miyamoto, N.
Author_Institution
Mitsubishi Electr. Corp., Tokyo, Japan
fYear
1993
fDate
7-10 Dec 1993
Firstpage
159
Abstract
Detecting of partial discharges (PD) in gas insulated switchgear (GIS) is an important monitoring process. This paper describes the study of behavior of a surge due to PD in GIS. PD can be detected by detecting the electromagnetic wave radiating from the insulated spacer enclosures, because the coaxial central conductor and the enclosure are not completely in the insulating spacer part. An antenna can detect the electromagnetic wave. By detecting several waves from different propagating paths in the same time, PD location in GIS can be estimated. This system is applied to 500 kV GIS
Keywords
charge measurement; electromagnetic wave propagation; gaseous insulation; magnetic variables measurement; partial discharges; surges; switchgear; 500 kV; GIS; antenna; coaxial central conductor; electromagnetic wave detection; gas insulated switchgear; insulated spacer enclosures; monitoring; partial discharge location;