Abstract
The electric field and potential distributions in the vicinity of non-ceramic insulators under dry and clean conditions are presented. A three-dimensional electric field analysis program, COULOMB, has been used for the calculations. A three-phase 765 kV power line tower geometry is considered for the potential distribution calculations along the insulators. For three-phase energization, two-dimensional contours of the three-dimensional equipotential surfaces are presented in selected vertical planes. The effects of the presence of power line conductors and of the three phase vs. single phase energization on the electric field and potential distributions have been investigated
Keywords
electric fields; insulators; power overhead lines; power system analysis computing; software packages; voltage distribution; 765 kV; COULOMB software; dry clean nonceramic insulators; electric field distributions; potential distributions; power line conductors; three-dimensional electric field analysis program; three-dimensional equipotential surfaces; three-phase energization; three-phase power line tower geometry; two-dimensional contours; Boundary element methods; Conducting materials; Conductors; Dielectrics and electrical insulation; Electric potential; Geometry; Permittivity; Poles and towers; Power system modeling; Shape;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, 2001. Proceedings
Conference_Location
Cincinnati, OH
ISSN
0362-2479
Print_ISBN
0-7803-7180-1
Type
conf
DOI
10.1109/EEIC.2001.965726
Filename
965726
Link To Document