• DocumentCode
    1920812
  • Title

    Cable Overheating in an Industrial Substation Feeder Due to Untransposed Power Cables - Measurement and Simulation

  • Author

    Gouramanis, K. ; Demoulias, C.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Thessaloniki Aristotle Univ.
  • Volume
    2
  • fYear
    2005
  • fDate
    21-24 Nov. 2005
  • Firstpage
    1438
  • Lastpage
    1441
  • Abstract
    This paper presents measurements of asymmetrical current distribution among parallel connected cables on the secondary side of 20/0.4kV transformers. Overloading of some cables is shown to lead to premature cable ageing. Simulation of the situation by EMTP shows that simple and affordable cable layout - other than cable transposition - can significantly deteriorate the current asymmetries. The increase in cable temperature and losses as well as the deterioration of cable useful life is calculated for various cable configurations
  • Keywords
    EMTP; industrial power systems; power cables; power measurement; power system simulation; substations; 20 to 0.4 kV; asymmetrical current distribution; cable layout; cable overheating; cable temperature; cable transposition; current asymmetries; industrial substation feeder; untransposed power cables; Aging; Current distribution; Current measurement; EMTP; Electrical equipment industry; Power cables; Power measurement; Substations; Temperature; Transformers; Cable simulation; EMTP; current distribution; current unbalance; power cables;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Computer as a Tool, 2005. EUROCON 2005.The International Conference on
  • Conference_Location
    Belgrade
  • Print_ISBN
    1-4244-0049-X
  • Type

    conf

  • DOI
    10.1109/EURCON.2005.1630233
  • Filename
    1630233