DocumentCode
1920812
Title
Cable Overheating in an Industrial Substation Feeder Due to Untransposed Power Cables - Measurement and Simulation
Author
Gouramanis, K. ; Demoulias, C.
Author_Institution
Dept. of Electr. & Comput. Eng., Thessaloniki Aristotle Univ.
Volume
2
fYear
2005
fDate
21-24 Nov. 2005
Firstpage
1438
Lastpage
1441
Abstract
This paper presents measurements of asymmetrical current distribution among parallel connected cables on the secondary side of 20/0.4kV transformers. Overloading of some cables is shown to lead to premature cable ageing. Simulation of the situation by EMTP shows that simple and affordable cable layout - other than cable transposition - can significantly deteriorate the current asymmetries. The increase in cable temperature and losses as well as the deterioration of cable useful life is calculated for various cable configurations
Keywords
EMTP; industrial power systems; power cables; power measurement; power system simulation; substations; 20 to 0.4 kV; asymmetrical current distribution; cable layout; cable overheating; cable temperature; cable transposition; current asymmetries; industrial substation feeder; untransposed power cables; Aging; Current distribution; Current measurement; EMTP; Electrical equipment industry; Power cables; Power measurement; Substations; Temperature; Transformers; Cable simulation; EMTP; current distribution; current unbalance; power cables;
fLanguage
English
Publisher
ieee
Conference_Titel
Computer as a Tool, 2005. EUROCON 2005.The International Conference on
Conference_Location
Belgrade
Print_ISBN
1-4244-0049-X
Type
conf
DOI
10.1109/EURCON.2005.1630233
Filename
1630233
Link To Document