• DocumentCode
    1977323
  • Title

    Research on interference characteristics of secondary cables due to lightning stroke in grounding grid of substation

  • Author

    Li Bing ; Xu Jianyuan

  • Author_Institution
    Sch. of Electr. Eng., Shenyang Univ. of Technol., Shenyang, China
  • fYear
    2013
  • fDate
    20-23 Oct. 2013
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The lightning current might inject grounding grid through the grounding lead when the arrester suffered a lightning wave in substation. Then the ground potential difference(the difference of ground potential can/may) generated interference voltage on secondary cables due to earth potential rising. The interference voltage might lead secondary equipments misoperation and even damage. To analysis the problems mentioned above, a equivalent circuit model was established. The transient voltage caused by ground potential difference to secondary cables could be (can be or is) calculated by EMTP-ATP. As a validation, the impulse voltage generator was used as voltage source to simulate that substation encountered with the lightning, and to measure the interference voltage at cable terminal as well. Both experiment and computer simulation had been taken to analysis the influencing factors of the interference voltage on secondary cables and the ports of secondary equipments. The factors included the lightning current injection point and the soil resistivity rate. The analysis would provide a reasonable reference for wiring cables to improve anti-jamming capability of secondary equipments in substation.
  • Keywords
    EMTP; arresters; earthing; electromagnetic interference; equivalent circuits; lightning protection; power cables; pulse generators; soil; substation protection; transients; wiring; EMTP-ATP; antijamming capability; arrester; equivalent circuit model; ground potential difference; grounding grid; impulse voltage generator; interference characteristics; lightning current injection point; lightning stroke; lightning wave; soil resistivity rate; substation; transient voltage; voltage source; wiring cables; Conductivity; Frequency modulation; Generators; Grounding; Lead; Soil; ground potential difference; interference voltage; lightning strike; secondary cable;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
  • Conference_Location
    Matsue
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2013.6804384
  • Filename
    6804384