• DocumentCode
    1990131
  • Title

    Protection system studies for ENEL Distribuzione´s MV loop lines

  • Author

    Lauria, Stefano ; Codino, Asia ; Calone, Roberto

  • Author_Institution
    DIAEE, “Sapienza” Univ. of Rome, Rome, Italy
  • fYear
    2015
  • fDate
    June 29 2015-July 2 2015
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The paper describes some of the fault studies performed for the protection system of ENEL Distribuzione´s experimental MV loop lines. The system consists of a pilot relaying scheme using directional overcurrent relays for ground and phase fault detection. With reference to an actual implementation (a MV distribution network including a loop line, in Southern Italy), attention is focused on phase fault detection, aiming at the determination of magnitude and phase angle settings for relays. The effects of fault location and fault resistance are investigated by detailed simulations, resulting in tentative phase relay settings for the new protection scheme.
  • Keywords
    distribution networks; overcurrent protection; power grids; power system protection; ENEL Distribuzione; MV distribution network; MV loop lines; Southern Italy; directional overcurrent relays; ground and phase fault detection; phase fault detection; pilot relaying scheme; smart grid; tentative phase relay; Delays; Green products; Indexes; RNA; Resistance; MV closed-loop; Protection system; Smart Grid; directional overcurrent; phase fault relaying;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    PowerTech, 2015 IEEE Eindhoven
  • Conference_Location
    Eindhoven
  • Type

    conf

  • DOI
    10.1109/PTC.2015.7232653
  • Filename
    7232653