• DocumentCode
    2033984
  • Title

    Partial discharge on-line measures in cable´s EPR insulation

  • Author

    Candela, R. ; Sanseverino, E. Riva ; Romano, P.

  • Author_Institution
    Dipt. di Ingegneria Elettrica, Palermo Univ., Italy
  • fYear
    2004
  • fDate
    17-20 Oct. 2004
  • Firstpage
    470
  • Lastpage
    473
  • Abstract
    In this paper, an experimental study, carried out on an operating MV cable, is presented. The aim is to identify, locate and characterize defects in the cable´s EPR (ethylene-propylene copolymer rubber) insulation. Direct partial discharge measurements have been compared to those obtained by high frequency electromagnetic field measures. The latter have been carried out using a sensor which does not require any galvanic connection with the system under test and that performs an intrinsic localization of the defect. Moreover, an analysis of an MV cable junction has been carried out using the same tools.
  • Keywords
    ethylene-propylene rubber; fault location; partial discharge measurement; power cable insulation; power cable testing; 20 kV; EPR cable insulation; MV cable junction; defect characterization; defect location; ethylene-propylene copolymer rubber; noncontact sensor; partial discharge on-line measurement; Cable insulation; Electromagnetic fields; Electromagnetic measurements; Frequency measurement; Paramagnetic resonance; Partial discharge measurement; Partial discharges; Rubber; Sensor phenomena and characterization; Sensor systems;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on
  • Print_ISBN
    0-7803-8584-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2004.1364289
  • Filename
    1364289